Protections
68
Display Reason
PLC Functions
If a PLC Function has been configured as a warning the appropriate
LCD message will be displayed and the COMMON ALARM LED will
illuminate.
S1 Failure Latch
The module has detected that S1 has failed for either an under/over
voltage/frequency condition. The latched alarm will not clear until the
START INHIBIT/RESET
button is pressed.
S1 Failure Unlatched
The module has detected that S1 has failed for either an under/over
voltage/frequency condition. The unlatched alarm will automatically clear
upon S1 returning to an available state.
S2 Failure Latch
The module has detected that S2 has failed for either an under/over
voltage/frequency condition. The latched alarm will not clear until the
START INHIBIT/RESET
button is pressed.
S2 Failure Unlatched
The module has detected that S2 has failed for either an under/over
voltage/frequency condition. The unlatched alarm will automatically clear
upon S2 returning to an available state.
7.3 ELECTRICAL TRIPS
Electrical trips are latching unload and stop S2 (if configured as a generator) but in a controlled
manner. On initiation of the electrical trip condition the module will de-energise the ‘Close S2 Output’
to remove the load from S2. Once this has occurred the module will start the Cooling timer and allow
the generator to cool down and shut off. The alarm must be accepted and cleared, and the fault
removed to reset the module.
Example
1/2 Alarm
Digital Input A
Latched
Electrical Trip
Electrical trips are latching alarms and unload and stop S2 (if configured as a generator). To clear
these alarms the START INHIBIT/RESET
button is pressed
Display Reason
Auxiliary Inputs
If an auxiliary input has been configured as an electrical trip, the
appropriate LCD message will be displayed and the COMMON ALARM
LED will illuminate.
Expansion Inputs
If an expansion input has been configured as an electrical trip, the
appropriate LCD message will be displayed and the COMMON ALARM
LED will illuminate.
PLC Functions
If a PLC Function has been configured as an electrical trip, the
appropriate LCD message will be displayed and the COMMON ALARM
LED will illuminate.