3.8.4 DSENET® FOR EXPANSION MODULES
DSENet® is the interconnection cable between the host controller and the expansion module(s) and
must not be connect to any device other than DSE equipment designed for connection to the
DSENet®
Cable type Two core screened twisted pair
Cable characteristic
impedance
120
Recommended cable Belden 9841
Belden 9271
Maximum cable length 1200m (¾ mile) when using Belden 9841 or direct equivalent.
600m (666 yds) when using Belden 9271 or direct equivalent.
DSENet® topology “Daisy Chain” Bus with no stubs (spurs)
DSENet® termination
120. Fitted internally to host controller. Must be fitted externally to the
‘last’ expansion module by the customer.
Maximum expansion
modules
Total 6 devices made up of DSE2130 (up to 2), DSE2157 (up to 2),
DSE2548 (up to 2)
This gives the possibility of :
Maximum 16 additional inputs (DSE2130)
Maximum 20 additional relay outputs (DSE2157)
Maximum 20 additional LED indicators (DSE2548)
NOTE: As a termination resistor is internally fitted to the host controller, the host
NOTE: As a termination resistor is internally fitted to the host controller, the host NOTE: As a termination resistor is internally fitted to the host controller, the host
NOTE: As a termination resistor is internally fitted to the host controller, the host
controller must be the ‘first’ unit on the DSENet®. A termination resistor MUST be fitted to
controller must be the ‘first’ unit on the DSENet®. A termination resistor MUST be fitted to controller must be the ‘first’ unit on the DSENet®. A termination resistor MUST be fitted to
controller must be the ‘first’ unit on the DSENet®. A termination resistor MUST be fitted to
thelast’ unit on the DSENet®. For connect
thelast’ unit on the DSENet®. For connectthelast’ unit on the DSENet®. For connect
thelast’ unit on the DSENet®. For connection details, you are referred to the section
ion details, you are referred to the section ion details, you are referred to the section
ion details, you are referred to the section
entitled ‘typical wiring diagramelsewhere in this document.
entitled ‘typical wiring diagramelsewhere in this document.entitled ‘typical wiring diagramelsewhere in this document.
entitled ‘typical wiring diagramelsewhere in this document.
3.9 ADDING AN EXTERNAL SOUNDER TO THE APPLICATION
Should an external alarm or indicator be required, this can be achieved by using the DSE
Configuration Suite PC software to configure an auxiliary output for “Audible Alarm”, and by configuring
an auxiliary input for “Alarm Mute” (if required).
The audible alarm output activates and de-activates at the same time as the module’s internal
sounder. The Alarm mute input and internal alarm mute button activate ‘in parallel’ with each other.
Either signal will mute both the internal sounder and audible alarm output.