Operation
61
6.7 MODE SELECTION
NOTE:
NOTE:NOTE:
NOTE:
If a digital input configured to
If a digital input configured to If a digital input configured to
If a digital input configured to
panel lock
panel lockpanel lock
panel lock
is active,
is active, is active,
is active, changing module modes will
changing module modes will changing module modes will
changing module modes will
not be possible. Viewing the instruments and event
not be possible. Viewing the instruments and eventnot be possible. Viewing the instruments and event
not be possible. Viewing the instruments and event
logs is NOT affected by panel lock.
logs is NOT affected by panel lock. logs is NOT affected by panel lock.
logs is NOT affected by panel lock.
Pressing the MODE
button sets which of the three modes below to leave the controller in.
6.7.1 TEST ON LOAD
Activate by pressing the MODE
button repeatedly until ‘Test on Load’ is shown on the display,
then press the TICK
button to confirm the change. An LED indicator beside the button confirms
this action.
The Test on Load mode will start S2 (if configured as a generator) and transfer the load to S2.
6.7.1.1 STARTING SEQUENCE
As soon as the MODE
is selected and confirmed by pressing the TICK
button is pressed,
the output to give a start signal to an external generator controller is activated (if S2 is configured as a
generator)
If the generator fails to start during the ‘S2 Fail Delay’ timer, an alarm will appear on the display which
shows Fail to Start. S2 is seen as available once the supply is within limits (if configured as a mains
supply) or had achieved loading voltage and frequency (if configured as a generator).
6.7.1.2 S2 AVAILABLE
In Test on Load mode, the load is automatically transferred to S2 when it is within limits (if configured
as a mains supply) or had achieved loading voltage and frequency (if configured as a generator).
If a start/load request is present but S2 will not go on load, an input configured to S2 Load Inhibit’
could be active.
NOTE:
NOTE: NOTE:
NOTE: The load transfer signal remains inactive until
The load transfer signal remains inactive until The load transfer signal remains inactive until
The load transfer signal remains inactive until S2 is seen as available
S2 is seen as availableS2 is seen as available
S2 is seen as available. This
. This . This
. This
prevents
prevents prevents
prevents loading to a supply that has failed or is not yet available
loading to a supply that has failed or is not yet availableloading to a supply that has failed or is not yet available
loading to a supply that has failed or is not yet available.
..
.
As the load increases and decreases, the module may (depending upon configuration) remove non-
essential loads. This is configured as part of the Load Shedding control settings in the DSE
Configuration Suite Software.
See section entitled Load Shedding elsewhere in this document for further details.
6.7.1.3 STOPPING SEQUENCE
In Test on Load mode, S2 will continue to run on load until either:
Pressing the START INHIBIT
button to return to start inhibit mode.
Pressing the AUTO
button to return to automatic mode.