Operation
59
6.6 AUTOMATIC MODE
NOTE:
NOTE:NOTE:
NOTE:
If a digital input configured to
If a digital input configured to If a digital input configured to
If a digital input configured to
panel lock
panel lockpanel lock
panel lock
is active,
is active, is active,
is active, changing module modes will
changing module modes will changing module modes will
changing module modes will
not be possible. Viewing
not be possible. Viewing not be possible. Viewing
not be possible. Viewing the instruments and event logs is NOT affected by panel lock.
the instruments and event logs is NOT affected by panel lock. the instruments and event logs is NOT affected by panel lock.
the instruments and event logs is NOT affected by panel lock.
Auto mode is activated by pressing the button.
In AUTO
mode, the module will operate fully automatically, changing between the two supplies in
case of failure without user intervention. An LED indicator beside the button confirms this action.
6.6.1 WAITING IN AUTO MODE
If a starting/loading request is made, the starting sequence will begin.
Starting/loading requests can be from the following sources:
S1 supply out of limits
Activation of an auxiliary input that has been configured to remote start on load or remote start
off load.
Activation of the inbuilt exercise scheduler.
Instruction from external remote telemetry devices using the RS232 or RS485 interface
6.6.2 STARTING SEQUENCE
To allow for ‘false’ start/load requests such as S1 brownouts, the start delay timer begins. There are
individual start delay timers for each of the different start/load request types.
Should all start/load requests be removed during the start delay timer, the unit will return to a stand-by
state.
If a start/load request is still present at the end of the start delay timer, an output to give a start signal
to an external generator controller is activated (if S2 is configured as a generator).
If the generator fails to start during the ‘S2 Fail Delay’ timer, an alarm will appear on the display which
shows Fail to Start. S2 is seen as available once the supply is within limits (if configured as a mains
supply) or had achieved loading voltage and frequency (if configured as a generator).
If a start/load request is present but the starting sequence has not begun, an input configured to Auto
Start Inhibit’ could be active.