Specification
12
3.6 DIGITAL INPUTS
Number
12 Configurable negative or positive switching inputs in banks of 3
through PC Software
Arrangement Contact between input terminal and the module’s plant supply
negative or positive terminal.
Low level threshold 3.2V minimum
High level threshold 8.1V maximum
Maximum input voltage +60V DC with respect to module’s plant supply negative terminal
Minimum input voltage -2V DC with respect to module’s plant supply negative terminal
Contact wetting current 7mA typical
Open circuit voltage 12V typical for negative activation.
0V typical for positive activation.
3.7 OUTPUTS
Twelve (12) outputs are fitted to the controller.
NOTE:
NOTE:NOTE:
NOTE:
Refer to
Refer to Refer to
Refer to Breaker Control Training Document (DSE part 056
Breaker Control Training Document (DSE part 056Breaker Control Training Document (DSE part 056
Breaker Control Training Document (DSE part 056-
--
-022
022022
022) for further
) for further ) for further
) for further
details on configuring and control
details on configuring and controldetails on configuring and control
details on configuring and control
different type of load switching devices
different type of load switching devicesdifferent type of load switching devices
different type of load switching devices.
..
.
3.7.1 CONFIGURABLE OUTPUTS A & E
Number 2
Type Fully configurable normally closed volt-free contacts.
Rating 8A resistive at 250V AC
3.7.2 CONFIGURABLE OUTPUTS B & F
Number 2
Type Fully configurable normally open volt-free contacts.
Rating 8A resistive at 250V AC
3.7.3 CONFIGURABLE OUTPUTS C & D
Number 2
Type Fully configurable volt-free changeover contacts.
Rating 8A resistive at 250V AC
3.7.4 CONFIGURABLE OUTPUTS G,H,I,J,K & L
Number 6
Type Fully configurable DC Outputs
Rating 2A resistive at DC supply voltage.