Operation
64
6.7.3.3 S2 AVAILABLE
In Prohibit Return mode, the load is automatically transferred to S2 when it is within limits (if
configured as a mains supply) or has achieved loading voltage and frequency (if configured as a
generator).
If a start/load request is present but S2 will not go on load, an input configured to ‘S2 Load Inhibit’
could be active.
A loading request can come from a number of sources.
• S1 supply out of limits
• Activation of an auxiliary input that has been configured to remote start on load
• Activation of the inbuilt exercise scheduler if configured for ‘on load’ runs.
NOTE:
NOTE: NOTE:
NOTE: The load trans
The load transThe load trans
The load transfer signal remains inactive until
fer signal remains inactive until fer signal remains inactive until
fer signal remains inactive until S2 is seen as available
S2 is seen as availableS2 is seen as available
S2 is seen as available. This
. This . This
. This
prevents
prevents prevents
prevents loading to a supply that has failed or is not yet available
loading to a supply that has failed or is not yet availableloading to a supply that has failed or is not yet available
loading to a supply that has failed or is not yet available.
..
.
As the load increases and decreases, the module may (depending upon configuration) remove non-
essential loads. This is configured as part of the Load Shedding control settings in the DSE
Configuration Suite Software.
See section entitled Load Shedding elsewhere in this document for further details.
If all start/load requests are removed, the stopping sequence will begin.
6.7.3.4 STOPPING SEQUENCE
In Return Inhibit mode, S2 will continue to run on load even if S1 has return until either:
• Pressing the START INHIBIT
‘ ’
button to return to start inhibit mode.
• Pressing the AUTO
‘ ’
button to return to automatic mode.