Front Panel Configuration
62
Part No. 057-120 8660 OPERATING MANUAL ISSUE 1 07/05/2010 ADM
7.3 ELECTRICAL TRIPS
Electrical trips are latching and stop the Generator but in a controlled manner. On initiation of the electrical trip
condition the module will de-energise the ‘Close Generator’ Output to remove the load from the generator. Once
this has occurred the start request is removed. The alarm must be accepted and cleared, and the fault removed to
reset the module.
Electrical trips are latching alarms and stop the Generator(s). Remove the fault then press Stop/Reset
to reset
the module.
Display Reason
AUXILIARY INPUTS If an auxiliary input configured as an electrical trip is active, the appropriate
message will be displayed as configured by the user.
kW OVERLOAD The measured Total kW is above the setting of the kW overload Electrical
Trip alarm
7.4 SCHEDULER
DSE8600 Series contains an inbuilt exercise run scheduler, capable of automatically starting and stopping the set.
Up to 16 scheduled start/stop sequences can be configured to repeat on a 7-day or 28-day cycle.
Scheduled runs may be on load or off load depending upon module configuration.
Example
Screen capture from DSE Configuration Suite
Software showing the configuration of the Exercise
Scheduler.
In this example the set will start at 09:00 on
Monday and run for 5 hours, then start at 13:30 on
Tuesday and run for 30 minutes.
7.4.1 STOP MODE
Scheduled runs will not occur when the module is in STOP/RESET mode.
7.4.2 MANUAL MODE
Scheduled runs will not occur when the module is in MANUAL mode.
Activation of a Scheduled Run ‘On Load’ when the module is operating OFF LOAD in Manual mode will have
no effect, the set continues to run OFF LOAD
7.4.3 AUTO MODE
Scheduled runs will operate ONLY if the module is in AUTO mode with no Shutdown or Electrical Trip alarm
present.
If the module is in STOP or MANUAL mode when a scheduled run begins, the engine will not be started.
However, if the module is moved into AUTO mode during a scheduled run, the engine will be called to start.
Depending upon configuration by the system designer, an external input can be used to inhibit a scheduled
run.
If the engine is running OFF LOAD in AUTO mode and a scheduled run configured to ‘On Load’ begins, the
set is placed ON LOAD for the duration of the Schedule.